MBR Membrane Modules & SUF – Capacity Guide (10 KLD → 100 KLD) | RRR ENVIRO SYSTEMS

MBR Membrane Modules & SUF — Capacity Selection Guide (10 KLD → 100 KLD)

Technical specs, module counts, flux, air scouring and P&ID integration. Use this page to select SUF/MBR modules for your project's flow and request pricing.

Why MBR / SUF Modules?

Membrane Bio-Reactors (MBR) combined with Submerged Ultra Filtration (SUF) modules deliver extremely fine solid-liquid separation (pore size ~0.06 µm), high-quality permeate & compact footprint. Ideal for reuse, ZLD pre-treatment, and tertiary polishing after conventional ETP/STP.

Capacity-wise Module Table (datasheet)

Table below is adapted from Memtrix SUF module datasheet you provided. For images & full P&ID see the P&ID section.

Capacity (KLD) No. of cassettes (@10 m² each) Size L×B×H (mm) Weight (Kg) Design flux (LMH) Air scouring (m³/h) Port size (Liquid/Air) Stand MOC
103310×640×16782115–256.01" / 1.25"SS304
206580×640×16782615–2512.01" / 1.25"SS304
308750×640×16782915–2516.01" / 1.25"SS304
40111120×640×16783615–2522.01.25" / 1.5"SS304
50141300×640×16783915–2528.01.25" / 1.5"SS304
60171660×640×16784515–2532.01.25" / 1.5"SS304
70191840×640×16784815–2538.01.25" / 1.5"SS304
80221070×1256×16785215–2544.01.25" / 1.5"SS304
90251250×1256×16786715–2550.01.5" / 1.5"SS304
100281340×1256×16786915–2556.01.5" / 1.5"SS304
Note: flux, air scouring and cassette counts are vendor datasheet values — final selection after pilot test & site-specific design.

10 KLD SUF Module — Quick Spec

Cassettes: 3 • Size: 310×640×1678 mm • Flux 15–25 LMH • Air 6 m³/h • Typical application: tertiary polishing for small STP/ETP.

50 KLD SUF Module — Quick Spec

Cassettes: 14 • Size: 1300×640×1678 mm • Flux 15–25 LMH • Air 28 m³/h • Typical application: MBR plant & UF polishing.

100 KLD SUF Module — Quick Spec

Cassettes: 28 • Size: 1340×1256×1678 mm • Flux 15–25 LMH • Air 56 m³/h • For larger MBR plants & industrial reuse.

P&ID / Process Flow Diagram

Below place your P&ID images (upload in WordPress media and replace the src paths). The P&ID shows: EQR, ART/MBR reactor, suction/permeate lines, blowers, backwash & chemical dosing lines.

MBR P&ID 1 — replace src with your file MBR P&ID 2 — replace src with your file
Tip: crop images to 1200px wide and upload to your media folder; the page will load faster.

Where to use MBR / SUF Modules

  • Municipal & apartment STP tertiary polishing (toilet flushing, gardening)
  • Industrial ETP polishing & ZLD RO pre-treatment
  • Hospitals, hotels, food processing for high quality reuse
  • Retrofit with existing aeration tanks + SUF module skid

Request Technical Proposal

Share: site location, required daily flow (KLD), raw influent BOD / TSS (if available) and any reuse requirement. We prepare GA, BOQ & performance guarantee after site visit or sample report.

WhatsApp

FAQ

Q: How do I pick the right module for my plant?
A: Start with daily flow (KLD). Pick the capacity row that is ≥ your required KLD and review flux & air requirements. Contact us for pilot testing if feed is foul or high TSS/TDS.

Q: What is air scouring?
A: Continuous or intermittent air scouring prevents membrane fouling — datasheet gives typical air m³/h per module stack.

Q: Can MBR modules be backwashed/chemically cleaned?
A: Yes — the modules support routine backwash (timing per vendor) and periodic chemical cleaning (NaOCl) as per datasheet.

RRR ENVIRO SYSTEMS · MBR & SUF Modules · Est. 2011 · ISO 9001:2015